Fire-Resistant Cable
0.6/1kV XLPE Insulated with Fire-Proof Layer and Tray Flame-Retardant PVC Sheathed Fire-Retardant Power Cable(TFR-8)
- ApplicationUsed for fire related equipment such as fire alarms, sprinkler system, emergency lighting circuits required fire - resistant properties.
- Construction- Conductors : Circular Stranded Annealed Copper
- Fire-Proof Layer : The Fire-proof Layer Shall be Applied Between
Conductor and Insulation
- Insulation : Cross-Linked Polyethylene(XLPE)
- Assembly : Multi-cores or Cable Shall be Assembled with a
Fire-protect Layer
- Sheath:FR PVC
- Core Identification:1core - black
2cores - black, white
3cores - black, white, red
4 cores - black, white, red, green - Fire-Resisting Test750℃/3hour
- StandardKS C IEC 60502-1 / KS C IEC 60332-3
0.6/1kV XLPE Insulated with Fire-Proof Layer and Tray Flame-Retardant PVC Sheathed Fire-Retardant Power Cable(TFR-8)
- ApplicationUsed for operation and interconnection of fire alarm and emergency information equipment.
- Construction- Conductors:Circular Stranded Annealed Copper
- Insulation : 90℃ Cross Linked Polyethylene (XLPE)
- Assembly : Multi-cores or Cable Shall be Assembled to Form
a Circular Cable with a Fire-protect Layer
- Fire - Proof Layer : The Fire-proof Layer Shall be Applied Between
the Assembly and Sheath
- Sheath : FR PVC
- Core Identification: Core Type 1 core white / 2 cores blue, red /
3 cores blue, red, white / 4 cores blue, red, white, white
Above 4 cores color tracer coding (Tracer color : blue, red)
Pair Type 1 pair blue-red / 2 pairs blue-white, red-white /
Above 3 pairs color tracer coding - Fire-Resisting Test380℃/3hour
- StandardKS C IEC 60502-1 / KS C IEC 60332-3